• LED test results indication
• quick access to the measurement procedures
• compact design and ergonomic soft case
• automatic measurement range selection
• measurement of protective conductor resistance with
the currents:
» PAT-2 • PAT-2E • PAT-10 | 200 mA,
» PAT-10 | 200 mA, 10 A
• insulation resistance measurement:
» PAT-2 • PAT-2E • PAT-10 | 250 V
» PAT-2E • PAT-10 | 250 V, 500 V
• PRCD trip time testing
• measurement of equivalent, touch and differential
leakage current
• measurement of mains voltage
• IEC lead test
• saving results to the memory
• printing labels with measurement results (option)
• works with software: Sonel Reader and Sonel
PAT Analysis
• works with Sonel PAT Analysis Mobile application
Capabilities
The PAT-10, PAT-2E and PAT-2 meters are an innovative combination of small
dimensions (allowing full mobility) with advanced measuring systems, providing
fully automatic measurements of electrical devices, IEC cables and extension
cords – also those with PRCD.
A set of tests is made with just one press of the START button. Configuration
options allow to modify meter’s work mode, and thus – to better tailor it to user’s
needs.
PAT instruments are equipped with a manual measurement mode. It is useful
in situations where individual test is sufficient instead of a complex measurement
sequence.
All instruments enable basic tests without external power supply: simplified
test sets are available in battery mode.
Small dimensions, light weight and a specially designed bag for the meter and
accessories provide both convenience and high mobility. Wireless communication
with the printer allows free measurement place arrangement without
tangled wires. Meter’s memory and integration with PC software additionally
extends the functionality of the instruments.
Standards
The tester can be used to test the equipment performance in accordance with
standards:
• EN 50699:2021 Recurrent tests of electrical equipment
• EN 60745-1 Hand-held motor-operated electric tools. Safety. General requirements
• EN 61029 Safety of transportable motor-operated electric tools – General requirements
• EN 60335-1 Household and similar electrical appliances -Safety – Part 1: General
requirements
• EN 60950 Safety of information technology equipment (IT Equipment)
• AS/NZS 3760:2010 In-service safety inspection and testing of electrical
equipment
• VDE 0404-1 Prüf- und Messeinrichtungen zum Prüfen der elektrischen Sicherheit
von elektrischen Geräten. Teil 1: Allgemeine Anforderungen
• VDE 0404-2 Prüf- und Messeinrichtungen zum Prüfen der elektrischen Sicherheit
von elektrischen Geräten. Teil 2: Prüfeinrichtungen für Prüfungen nach
Instandsetzung, Änderung oder für Wiederholungsprüfungen
• VDE 0701-0702 Prüfung nach Instandsetzung, Änderung elektrischer Geräte.
Wiederholungsprüfung elektrischer Geräte. Allgemeine Anforderungen für die
elektrische Sicherheit
Sonel PAT Analysis Mobile
The mobile application extends the capabilities of Sonel
PAT-10, PAT-2E, PAT-2 testers series. It available on devices
with Android operating system (version 5.0+).
Sonel PAT Analysis Mobile:
• connects wirelessly to the selected tester and printer,
• downloads measurement results,
• saves results to PAT memory structure (client, appliances
and measurement data),
• prints reports and QR codes,
• reads QR codes of the PAT system,
• sends data via internet.
Sonel PAT Analysis
This software is intended for companies that perform
safety measurements of electrical equipment.
Applications are compatible with Sonel PAT-series testers.
Data saved by the meter is entered into the test report for
the selected item of equipment.
• Perfect for production plants, electrical tool rental services,
repair and maintenance services, etc.
• Hierarchical data entry structure – a device is assigned to a
specific company or department.
• Capability of gathering information about a given piece of
equipment.
• Tracking the test history of a device.
• Capability of advanced meter configuration via software.
• Label printing on standard adhesive papers.
• Capability of creating a custom measurement standard using
the report editor.
• Capability of scheduling measurements – every device contains
a “Measurement cycle” list – the application automatically
displays devices whose testing deadline is approaching
or has expired.
Report printing according to the following standards:
• VDE 0701:1, VDE 0701:200, VDE 0701:240, VDE 0701:260,
DIN VDE 0702, EN 61010, EN 60335, EN 60950, IEC 60601,
EN62353
Specifications
Model PAT-10 PAT-2E PAT-2
Visual test √ √ √
Resistance measurement of PE conductor I = 200 mA 0.01…19.99 Ω 0.01…19.99 Ω 0.01…19.99 Ω
Resistance measurement of PE conductor I = 10 A 0.01…1.99 Ω – –
Insulation resistance measurement U = 250 V 0.25…99.9 MΩ 0.25…99.9 MΩ –
Insulation resistance measurement U = 500 V 0.50…99.9 MΩ 0.50…99.9 MΩ 0.50…99.9 MΩ
Measurement of substitute leakage current 0.01…19.9 mA 0.01…19.9 mA 0.01…19.9 mA
Measurement of touch leakage current 0.001…4.999 mA 0.001…4.999 mA –
Measurement of differential leakage current 0.10…19.9 mA 0.10…19.9 mA –
IEC cord test (RISO, RPE, polarity) √ √ √
PRCD test (tripping time for IΔn: x1/x5; 0° and 180°) 10 mA, 30 mA 10 mA, 30 mA –
Built-in memory for results / transmission to
computer
√ √ √
Wi-Fi √ √ √
Compatible with printer √ √ √
Meter configuration from computer √ √ √
Power supply
Network power supply:
220 V; 230 V; 240 V 50/60 Hz
Built-in rechargeable battery
Network power supply:
220 V; 230 V; 240 V 50/60 Hz
Built-in rechargeable battery
Built-in rechargeable battery
(measurements can be
performed during charging)
Measurement category CAT II 300 V √ √ √
Weight ca. 1.40 kg
Dimensions 200 x 180 x 77 mm
Measurement standards EN 50678, EN 50699