• Measuring voltage in the range of 50…5000 V, 50…1000 V in steps of 10 V, 1…5 kV in steps of 25 V
• Continuous indication of measured insulation resistance and leakage current
• Automatic discharge of measured object capacitance voltage after the end of insulation resistance measurement
• Acoustic signalling of 5-second intervals to facilitate capturing time characteristics
• Adjustable measuring time – max. 99’59’’
• Metered T1, T2 and T3 test times for measuring one or two absorption coefficients from the range of 1…600 s
• Measurement of coefficients: polarisation (PI), absorption Ab1, Ab2, dielectric absorption ratio (DAR)
• Indication of actual test voltage during measurement
• Test current: 1.2 mA or 3 mA
• Two- and three-lead method of insulation resistance measurement
• Measurements with test leads up to 20 m
• Protection against measuring live objects
• Measurement of capacitance during the measurement of RISO
• Step voltage insulation resistance measurement (SV)
• Dielectric Discharge calculation (DD)
• Digital filters for measurements with strong interferences
Additional features
• MIC-5010 | Continuity measurement of protective connections and equipotential
bonding in accordance with EN 61557-4 with current > 200 mA
• MIC-5010 | Adjustable limits for measured insulation resistance
• MIC-5010 | Adjustable limits for measured RCONT resistance
• High resistance to interferences – digital filters (10 s, 30 s, 60 s)
• Measurement of capacitance during the measurement of RISO
• Measurement of leakage current during insulation resistance testing
• DC and AC voltage measurement in the range of 0…600 V
• 990 cells of memory (11880 records) with the capability of wireless data
transmission to a PC (with Bluetooth) or via USB cable
• Power supply from mains or battery pack
• Backlit display
• Backlit keys
• The instruments meet the requirements of the EN 61557 standard
Comparison of meters
MIC-5010 MIC-5005
maximum measuring voltage 5000 V 5000 V
maximum measuring range 15 TΩ 15 TΩ
resistance to external interference voltages up to 500 V up to 500 V
advanced, digital interference filtration 10 / 30 / 60 seconds 10 / 30 / 60 seconds
continuity measurement of protective conductors √
Capacitance measurement
Display range Resolution Accuracy
0…999 nF 1 nF
±(5% m.v. + 5 digits)
1.00…49.99 μF 0.01 μF
• Capacitance measurement result is displayed after the RISO measurement
• For measurement voltages below 100 V the measurement error is not
specified
Insulation resistance measurement
• Measuring range according to IEC 61557-2
RISOmin =UISOnom /IISOmax=50 kΩ…15.0 TΩ (IISOmax =1.2 mA or 3 mA)
Display range Resolution Accuracy
0…999 kΩ 1 kΩ
±(3% m.v. + 10 digits)
1.00…9.99 MΩ 0.01 MΩ
10.0…99.9 MΩ 0.1 MΩ
100…999 MΩ 1 MΩ
1.00…9.99 GΩ 0.01 GΩ
10.0…99.9 GΩ 0.1 GΩ
100…999 GΩ 1 GΩ ±(3.5% m.v. + 10 digits)
1.00…9.99 TΩ 0.01 TΩ ±(7.5% m.v. + 10 digits)
10.0…15.0 TΩ 0.1 TΩ ±(10% m.v. + 10 digits)
Values of measured resistance depending on measuring voltage
UISO voltage Measuring range
250 V 500 GΩ
500 V 1 TΩ
1000 V 2.00 TΩ
2500 V 5.00 TΩ
5000 V 15.0 TΩ
MIC-5010 | Continuity test with current >200 mA
• Measuring range according to IEC 61557-2: 0.12…999 Ω
Display range Resolution Accuracy
0.00…19.99 Ω 0.01 Ω
±(2% m.v. + 3 digits)
20.0…199.9 Ω 0.1 Ω
200…999 Ω 1 Ω ±(4% m.v. + 3 digits)
• Current flowing bidirectionally, average resistance is displayed on the
screen
• Compensation of test leads resistance, autozeroing
Technical specification
type of insulation acc. to EN 61010-1 and IEC 61557 double
measurement category acc. to EN 61010-1 IV 600 V (III 1000 V)
ingress protection acc. to EN 60529 IP67 (IP40 for open case)
power supply
LiFePO4 13.2 V 5.0 Ah rechargeable battery
90 V…260 V, 50 Hz/60 Hz from electric grid
dimensions 390 x 308 x 172 mm
15.3″ x 12.1″ x 6.8″
weight ca. 6 kg
ca. 13.2 lbs
storage temperature -25°C…+70°C
-13°F…+158°F
operating temperature -20°C …+50°C
-4°F…+122°F
humidity 20%…90%
operating altitude ≤3000 m
reference temperature +23ºC ± 2ºC
reference humidity 40%…60%
display segment LCD
number of RISO measurements acc. to EN 61557-2 with battery power supply min. 1000
data transmission USB, Bluetooth
quality standard ISO 9001, ISO 14001, PN-N-18001 compliant
device meets the requirements of standards EN 61010-1 and IEC 61557
the product meets EMC requirements (immunity for industrial environment) with accordance to standards EN 61326-1 and EN 61326-2-2